1250SM0904R10/09 C-Bus™ Basic Programming
10/2009 C-Bus™ Products Training Course
© 2009 Schneider Electric. All Rights Reserved. 107
Recovery Tab
The Recovery tab affects the behaviour of each dimmer channel on power
up.
If the C-Bus dimmer loses it mains power, the unit will shut down. When
mains power is restored to the C-Bus dimmer, the channels will (by default)
restore to the previously known levels after the specified delay period
(default 5 seconds).
By removing the tick from a relay channel’s check box, the following
behaviours may be programmed into each individual channel, after mains
power is restored:
turn ON (100%)
turn OFF (0%)
set level using the slider (1% to 99%).
Figure 92 - The Recovery tab of a dimmer
Global Tab
The Global tab allows various parameters to be configured for the entire
relay unit.
Figure 93 - The Global tab of a dimmer