C-Bus™ Basic Programming 1250SM0904R10/09
C-Bus™ Products Training Course 10/2009
122 © 2009 Schneider Electric. All Rights Reserved.
Toggle If the output is currently off, it is set to the maximum level. Otherwise it is
switched off. An ON or OFF message is transmitted over the C-Bus
network.
On Key If the output is off, it is set to the maximum level. Otherwise no action is
taken. An ON message may be transmitted over the C-Bus network.
Off Key If the output is not off, it is switched off. Otherwise no action is taken. An
OFF message may be transmitted over the C-Bus network.
End Ramp The ramping action initiated by a Downcycle, Down Key or Up Key
function is terminated. This allows an output to be set at an intermediate
level. A RAMP TO LEVEL message is transmitted over the C-Bus
network.
Table 43 - The different type of micro functions
Passive Infrared Sensors
Before programming a PIR, it is important to adjust the Light Level Trimpot
for the appropriate light level which it is to operate in. When the Light Level
Trimpot (which is physically located on the PIR) is adjusted:
Fully clockwise, the PIR will only detect in darkness.
Fully anticlockwise, the PIR will detect when natural light is present.
To a midpoint to achieve a finer and more specific light level threshold.
PIR Programming
To begin programming a passive infrared (PIR) sensor, double click on the
PIR in the Database or Network section of the Programming window. This
will open the GUI of the PIR sensor.
Figure 107 - The Passive Infrared (PIR) Sensor GUI